WITTE SOFTWARE

Updated 11 days ago
  • ID: 7762401/148
Marianevej 87 7800 Skive Denmark
MODBUS© Protocol is a messaging structure, widely used to establish master-slave communication between intelligent devices. A MODBUS message sent from a master to a slave contains the address of the slave, the 'command' (e.g. 'read register' or 'write register'), the data, and a check sum... If the slave makes a normal response, the function code in the response is an echo of the function code in the request. The data bytes contain the data collected by the slave, such as register values or status. If an error occurs, the function code is modified to indicate that the response is an error response, and the data bytes contain a code that describes the error. The error check field allows the master to confirm that the message contents are valid... In ASCII mode, messages start with a colon ( : ) character (ASCII 3A hex), and end with a carriage return-line feed (CRLF) pair (ASCII 0D and 0A hex).
Also known as: modbus tools
VAT numbers: DK29277311
Primary location: Skive Denmark
  • 0
  • 0
Interest Score
3
HIT Score
0.00
Domain
modbustools.com

Actual
www.modbustools.com

IP
185.21.41.218

Status
OK

Category
Other

People Also Viewed


  1. DALEREAM LIMITED
  2. STAGE MALTA - stagemalta.org
  3. WALBERG AND AUGE - walbergandauge.com
  4. MEDSAAS - medsaas.io
  5. DENT DYNAMIC - dentdynamic.com
0 comments Add a comment